CONSUMPTION PROTEC


 TABLE 1 - ADDRESSABLE ELEMENTS - CONSUMPTION

 MODEL ADDRESSABLE UNITS  CONSUMPTION IN WORKING STATE (mA)  CONSUMPTION IN ALARM STATE (mA)
 6000/ASB2 BASE OF THE SIREN ADDRESSED IN A LOOP 0.55  5
6000/ASBEA2   BASE OF THE SIREN ADDRESSED IN A LOOP WITH A FLASHING LIGHT 0.6 10
 6000/BGK GLASS BREAKAGE 0.5  0.8 
 6000/ION IONIZING SMOKE DETECTOR  0.52  0.8 
 6000/OP OPTICAL SMOKE DETECTOR  0.55  0.85
 6000/0PHT  OPTICAL HEAT DETECTOR 0.58 0.88 
 6000/TEMP  TEMPERATUR EDETECTOR 0.48  0.78 
 6000/SYS2R RED SYMPHONY SIREN  0.5 
 6000/SRZ2 SIREN ADDRESSED IN A LOOP  0.5  20 
 6000/PVR2 LIGHT ADDRESSED IN A LOOP 0.5 45 
 6000/SRZ2/PVR  LIGHT OF THE SIREN ADDRESSED IN A LOOP 0.5  75 
 6000/MICCO   1.3 
 6000/CCO   0.6 10 
 6000/MIP   0.65 
 6000/BEAM BEAM DETECTOR 15   25
 6000/ATSB2 BASE OF THE SIREN WITH SPEECH 0.7  10 
 6000/SSR2 SYSTEM SIREN  0.65 

 

TABLE 2 - ADDRESSABLE ELEMENTS WITH AUXILIARY POWER SUPPLY - CONSUMPTION

MODEL  ADDRESSABLE UNITS

IN WORKING STATE (mA) 


IN THE LOOP

 IN WORKING STATE (mA)


24V

IN ALARM STATE (mA)


IN THE LOOP

IN ALARM STATE (mA)


24V

 6000/ASB4 BASE OF THE SIREN ADDRESSED IN A LOOP WITH AUXILIARY POWER SUPPLY 0.58  1.5 
 6000/ASBEA4 BASE OF THE SIREN ADDRESSED IN A LOOP WITH AUXILIARY POWER SUPPLY 0.58 1.5  
 6000/SRZ4  SIREN ADDRESSED IN A LOOP WITH AUXILIARY POWER SUPPLY 0.5  20 
 6000/PVR4  LIGHT ADDRESSED IN A LOOP WITH AUXILIARY POWER SUPPLY 0.5 2 45 
 6000/SRZ4/PVR

 SIREN LIGHT ADDRESSED IN A LOOP WITH AUXILIARY POWER SUPPLY

0.5  75 
 6000/ZA ALARM ZONES 0.6  35+     alarm load
 6000/16WAY2

 

 18+ load zone + output plate load   (5A max)  

 18+ zone load + output plate load (5A max)

 

TABLE 3 - NON ADDRESSABLE ELEMENTS - CONSUMPTION

MODEL NON ADDRESSABLE UNITS

IN WORKING STATE (mA) 


IN THE LOOP

IN WORKING STATE (mA)  


24V

IN ALARM STATE(mA) 


IN THE LOOP

IN ALARM STATE   (mA)


24V

6000/SB BASE OF THE SIREN 24V  -
 6000/SBEA  BASE OF THE SIREN 24V WITH A LIGHT  - -  
6000/FIU     0.12 - 0.12  -
 6000/IU    0.12 - 0.12 -
6000/DIB  INSULATOR DOUBLE BASE 0.12 - 0.12 -
6000/BASE STANDARD BASE - - - -
6000/RBNC ili 6000/RBNO  RELAY BASE   0.05 - 15  -


 

LOGIN
you are not logged in
e-mail address:
password:

Forgot your password?   

SEARCH
Enter a word or phrase:

NEWSLETTER
Enter your e-mail address:

TESLA SISTEMI
The team on the field

 


 

 


CATALOG
 View the catalog Tesla systems »

ISO 9001

 

 

ISO 14001

 

 

ISO 18001

 

 

ISO 20000

 

 

ISO 22301

 

 

ISO 27001

 

 

ISO 50001

 

 

Control Certificate

 

 


NIKOLA TESLA
www.tesla-museum.org »